Abstract
A model predictive controller was implemented at the flash drying unit of the Anglo American Platinum Polokwane smelter. The controller uses a mix of standard model predictive control technology and dynamic control limits (based on the rate of change of the hot gas generator average bed temperature) to improve temperature stability across the unit. The improved temperature control resulted in the ability to process 1.80% more concentrate through the unit without the need to increase coal feed, as well as reducing the number of coal feeder trips that result from high temperature events.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.