Abstract
This paper presents a general method for building equivalent electric circuits of power transformers, including eddy current effects in windings and core. A high-frequency equivalent dual model for single- and three-phase transformers with two multilayer windings is derived from the application of the principle of duality. The model is built from elements available in circuit simulation programs, such as Electromagnetic Transients Program (EMTP)–Alternative Transients Program, EMTP-RV, PSCAD, and PSpice. The parameters of the frequency-dependent leakage inductance and winding resistance are computed with analytical formulae obtained from the solution of Maxwell’s equations that are based on the geometrical dimensions and material information. Ideal transformers are utilized to isolate the electric components (winding resistors and capacitors) from the magnetic components (inductors). The physically correct connection points for electric and magnetic components are clearly identified. The proposed methodology is successfully validated versus finite- element simulations and laboratory measurements.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.