Abstract

In order to understand the impingement flow field and cooling characteristics of vectoring dual synthetic jets (DSJ), an experimental investigation was performed to analyze the parameter effects. With the variation of the slot location, the vectoring angle of DSJ can be adjusted from 34.5° toward the left to 29.5° toward the right. The vectoring function can greatly extend the length of impingement region. There are three local peaks both for the local cooling performance (Nu) and the whole cooling performance (Nuavg). Although the peak Nu at a certain location of the slider is higher than that at the center, the corresponding Nuavg is lower. As for different driving frequencies, the vectoring angle reaches its minimum of 9.7° at 350 Hz, but the Nu is obviously improved. There is one local peak of Nuavg values at 350 Hz rather than three local peaks at 250 Hz and 450 Hz. The slot locations where the Nuavg of 250 Hz and 450 Hz reach maximum are different. With the increase in driving voltage from ±100 V to ±200 V, the vectoring angle drops from 46.9° to 22.2°, but both Nu and Nuavg are improved. The maximum Nuavg of each driving voltage occurs at the center location of the slider. The choking effect and the cross flow have dominated the vectoring angle and the cooling performance of impingement DSJ. Vectoring DSJ will give impetus to the thermal management of large-area electric devices in spaced-constrained cooling and removing dynamic hotspots.