Abstract
Phase selection is a significant protection element, which determines faulty phase(s). However, commercial phase selection methods (PSMs) are susceptible to failure in the presence of inverter-interfaced resources (IBRs) because their fault currents possess different characteristics than conventional generation sources. This paper develops a dual current controller (DCC) in the stationary frame to make the traditional current-angle-based PSM operate correctly at the relay location without frame transformation. First, the fault type is determined at the IBR. Then, the reference angle of the negative-sequence current is determined to achieve the current-angle-based PSM requirements. Subsequently, the negative-sequence current reference in the stationary frame is determined according to its current reference angle and its maximum current limit. Besides, the positive-sequence current is determined based on the active and reactive current references. Lastly, the sinusoidal reference currents are tracked accurately using a proportional-resonant (PR) control. Comprehensive time-domain simulations are used to validate the accuracy of the proposed DCC under different fault conditions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.