Abstract

A new hybrid control technique called gradient descent back propagation (GDBP)-based φ for a three phase two-level distribution static compensator (DSTATCOM) to perform the functions such as harmonic mitigation, power factor correction under reactive loads, which further reduces the DC link voltage across the self-supported capacitor of voltage source converter (VSC). The weighted value of fundamental active and reactive components of load currents are extracted using the proposed control technique to generate the reference source currents. Furthermore, these currents are used to trigger the VSC of the DSTATCOM. The effectiveness of this control technique is demonstrated through simulation using MATLAB/SIMULINK and sim power system tool boxes. The real-time implementation of DSTATCOM is also realised by real-time digital simulator. These results reveal the robustness of the proposed DSTATCOM as it is showing outstanding harmonic compensation capabilities under the various loading conditions and keeping the total harmonics distortion of the source current well <;5%, the limit imposed by IEEE-519 standard.