Abstract

This paper exploits an electrical characteristic of distribution networks to cast the state estimation problem into a sparse vector recovery problem. In distribution networks, voltage differences between two buses of each line segment are much smaller than the infeed bus voltage. Therefore, the voltage profile signal can be sparsified with a difference transformation and recovered from only a few micro-phasor measurement units (μPMUs) using compressive sensing (CS) and ℓ1 regularization. The effectiveness of the proposed algorithm is verified through the simulation results of a standard unbalanced distribution network, the IEEE 123-bus system, under different operation conditions. The method accurately estimates system states even with multiple bad current measurements. It also detects, identifies, and corrects bad voltage measurements. In addition, a problem of binary integer linear programming is solved to obtain and optimally place the minimum number of μPMUs necessary to provide a unique solution for the proposed state estimation formulation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.