A high-voltage AC double-circuit 400 kV overhead power transmission line runs from the city of Elk (Poland) to the city of Alytus (Lithuania). This international 400 kV power transmission line is potentially one of the strongest magnetic field-generating sources in the area. This 400 kV voltage double-circuit overhead transmission line and its surroundings were analyzed using the mathematical analytical methods of superposition and reflections. This research paper includes the calculation of the numerical values of the magnetic field and its distribution. The research showed that the values of the magnetic field strength near the international 400 kV power transmission line exceed the threshold values permitted by relevant standards. This overhead power line is connected to the general (50 Hz) power system and generates a highly intense magnetic field. It is suggested that experimental trials should be undertaken in order to determine the maximum values of the magnetic field strength. For the purpose of mitigating these values, it is suggested that the height of the support bars should be increased or that any individual and commercial activities near the object under investigation should be restricted.

Highlights

  • The institutions involved in electric power transmission in Lithuania and Poland have decided to implement the electricity link “LitPol Link”

  • As the strongest magnetic field in the electrical power system can be generated by the double-circuit 400 kV power transmission line, it is necessary to determine how the magnetic field is distributed in the surroundings of this overhead power transmission line

  • The magnetic field strength of this power line was found to exceed the numerical values permitted by the Hygiene Standard HN 104:2011 HN, revealing that any person living or working in these areas was in serious danger

Read more

Summary

Introduction

The institutions involved in electric power transmission in Lithuania and Poland have decided to implement the electricity link “LitPol Link”. The recently adopted Hygiene Standard HN 104:2011 “Human protection against electromagnetic fields caused by overhead power lines” is currently valid in the European Union (EU) and states that the effective values of the magnetic field strength must never exceed exceed 32 A/m or 40 μT (magnetic flux density) in residential environments, or 16 A/m or 20 μT (magnetic flux density) within residential and public service buildings. These values should never be exceeded irrespective of the duration of a person’s exposure to an electromagnetic field. Sci. 2020, 10, 3266 overhead transmission line in order to prevent the magnetic field generated by this power transmission line from exceeding the requirements set by the European Union (EU) Hygiene Standard HN 104:2011

Extra High-Voltage Double-Circuit Electric Power Transmission Line
Magnetic Field Generated by the Single Thin Current Lead
Analysis of Magnetic Field from 400 kV AC Power Transmission Line
Findings
Discussion
Conclusions