Solar photovoltaics in electricity distribution networks is often limited by the rise in voltage magnitude. The pre-connection voltage magnitude is an important factor that determines the hosting capacity.This paper studies to which extent details of the pre-connection voltage magnitude impact the hosting capacity. Extensive measurements of voltage magnitude and solar power production were obtained for a number of distribution networks with 10-minute resolution. The measured background voltage during the sunny-hours from the two-year measurements was used to obtain representative probability distribution functions. A guide for selecting the time-of-day (ToD) used is presented.The obtained probability distribution functions are applied to estimate the stochastic hosting capacity for a low-voltage distribution network with 83 customers. The impact of various details on the hosting capacity are studied.The results show that general knowledge about the range of the pre-connection voltage are essential for the hosting capacity estimation. Measurements over one year were shown to be sufficient to estimate the hosting capacity. The hosting capacity considering the entire day was underestimated by 11 % when compared to the 10 am – 2 pm sunny-hours. The proposed method is general and can be applied to other aleatory uncertainties and other types of hosting capacity studies.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.