Abstract

Distribution arrester failures have been thought to be caused by direct or nearby strokes. We have, however, found that distribution arrester failure is caused by part of the current which flows into distribution lines when the customer's structure is struck by lightning. We call this current lightning backflow In order to clarify the influence of backflow current on arrester failure, we have conducted experimental and analytical studies and observed the distribution outages. The main results are as follows. (1) The calculated failure probability of an arrester caused by backflow current in winter is almost equal to that caused by a direct stroke to distribution lines. (2) According to the investigation of lightning-caused failures, about half of the arrester failures are due to backflow current. (3) Lightning backflow current should be considered as one of the main causes of distribution arrester failures.