Abstract

Conservation voltage reduction (CVR) is implemented in the distribution system to reduce the voltage along the feeder with the objective to reduce the power consumption. Due to the increased penetration of distributed generators in the distribution system the centralized control is cumbersome. Hence, in this paper, a distributed algorithm is proposed for volt-var optimization (VVO) with CVR objective in a three-phase unbalanced distribution network. The proposed method is based on alternating direction method of multipliers (ADMM) algorithm. Mathematically the problem is formulated as a convex optimization problem with reactive power support from smart inverters. The convexity guarantees the solution obtained using the proposed method is a converged solution. The proposed method is validated on IEEE 4-bus and 13-bus three-phase unbalanced systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.