Abstract
This article presents a directional relaying algorithm based on a voting technique for the protection of a series-compensated line where the capacitors are present at both the ends of the line. The directional relaying issues in a series-compensated line related to voltage inversion, current inversion, high-resistance fault, and load change are addressed. Four classifiers based on positive- and negative-sequence components are selected and integrated using the voting technique to derive the final decision. The technique is evaluated using data simulated with EMTDC/PSCAD (Manitoba Hydro) for a series-compensated line, and the dynamic performance of the algorithm is also studied. The integration approach is found to be advantageous.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.