Abstract

This paper investigates shear flow strength of insulated concrete sandwich panels with glass fiber reinforced polymer (GFRP) shear connectors based on push-out test. The precast insulated concrete panels consist of 60mm concrete wall, 100mm insulation, and 130mm concrete wall. Two concrete walls were connected with GFRP corrugated shear connector. Four specimens with variables such as the insulation type and the width of GFRP corrugated shear connector were made. Failure modes, shear flow-deflection relationships and post-peak strength were investigated. Test results indicate that the specimens with EPS insulation show higher shear flow strength than those with XPSS insulation due to the relatively high surface roughness of EPS insulation, and the shear flow strength increased with increasing shear connector width.