Abstract
Indoor contaminant removal over 0.5 ≤ FrT ≤ 5.0, 0.5 ≤ N ≤ 5.0, and 50 ≤ Re ≤ 500 was investigated numerically, wherein FrT refers to the Froude number, N refers to the buoyancy ratio, and Re refers to the Reynolds number. As demonstrated, the ventilation effectiveness increased with increasing contaminant source intensity and air supply intensity at a constant air temperature, indicating that increase the fresh air can effectively eliminate contaminants in this case. At high air supply temperatures, the heat retention time and contaminant transport was extremely short, and the fresh air induced by strong natural convection floating lift was rapidly discharged. Additioanlly, the air supply intensity had significant effects on contaminant removal. Quantification of the ventilation effectiveness under the combined effects of air supply intensity, air supply temperature and contaminant source intensity was determined based on the results of direct numerical simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.