Abstract
The interaction of rocket-triggered lightning with two unenergized power distribution lines of about 800 m length was studied at the International Center for Lightning Research and Testing in Florida. A horizontally configured line was tested in 2000, and a vertically configured line in 2001, 2002, and 2003. The horizontally and vertically configured lines were equipped with six and four arrester stations, respectively, and, additionally, in 2003, the vertical line with a pole-mounted transformer. During the 2000, 2001, and 2002 experiments, arresters were frequently rendered inoperable by disconnector operation during triggered lightning strokes, but there was no disconnector operation during the 2003 experiment when the transformer was on the line. In all four years, there were commonly flashovers from the struck phase-conductor to the closest phase-conductor not subjected to direct lightning current injection. The self-consistency of measurements is assessed via comparison of the injected lightning current with: 1) the total current flowing to Earth through the multiple line groundings and 2) the total phase-to-neutral current flowing through the line arresters and line terminations. This paper is part one of two related papers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.