Abstract

Data centers consume an ever-increasing amount of electricity because of the rapid growth of cloud computing and digital information storage. A high voltage point of load (HV POL) converter is proposed to convert the 400-VDC distribution voltage to 1-VDC within a single stage to increase the power conversion efficiency. A six-phase input series output parallel (ISOP) connected structure is implemented for the HV POL. The symmetrical controlled half bridge current doubler is selected as the converter topology in the ISOP structure. The full load efficiency is improved by 4% points compared with state of the art products. A voltage compensator has been designed in order to meet the strict dynamic voltage regulation requirement. A laboratory prototype has been built, and experimental results have been provided to verify the proposed HV POL with a single power conversion stage can meet the dynamic voltage regulation requirement for an on-board power supply with higher efficiency compared to the conventional architecture.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call