Abstract

Power system control and protection equipment has required higher sensitivity and operational reliability than conventional one. Studies of digital signal processing suitable for electric power systems fulfill this objective using fast sampling and digital filtering by a 32-bit floating point DSP (Digital Signal Processor). The sampling rate of 3 kHz is carefully selected in order to separate the power spectrums of the A-D conversion output errors from the signal bandwidth. The new 12-bit A-D conversion unit equipped with a recursive-type digital filter achieved the equivalent high resolution of 14-bit conversion. This paper describes the design concept and the characteristics showing applications to current differential relays, distance relays and power system controllers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.