Abstract

Frequency, amplitude, and phase information of the grid voltage are the main constraints for constructing a robust controller algorithm for grid connected applications under unbalanced and distorted voltage conditions. This paper narrates a simple, robust, straight forward method to estimate the instantaneous positive and negative sequence voltage components under unbalanced and distorted voltage circumstances. A second order generalized integrator (SOGI) is encapsulated to filter out the distorted voltage as well as to generate orthogonal voltage components for the three phases of AC grid. Furthermore, these filtered and orthogonal components are accounted for the calculation of instantaneous symmetrical components. Developed technique is more frequency adaptive compared to conventional phase locked loop (PLL) techniques. A set of test outcome results are provided in this paper based on MATLAB/Simulink simulations with real grid data captured from an industrial plant. Moreover, SOGI based estimator is digitally implemented by using dSPACE ds1103 digital controller to validate the numerical simulation results in accordance with the developed theoretical prediction.