Abstract
The author reviews methods of calibrating low-differential (25–300 in. H2O) D.P. transmitters at high (up to 3000 psig) static pressure. Various test methods are described along with discussion of their merits. Included are use of one or more deadweight testers (gas or liquid) and use of a high-pressure mercury manometer as a standard. Five D.P. transmitters of different construction are tested and their static span-shift performance reported.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.