Abstract

The fault location algorithm based on a differential equation-based approach for a transmission line employing a unified power flow controller (UPFC) using synchronised phasor measurements is presented. First, a detailed model of the UPFC and its control is proposed and then, it is integrated into the transmission system for accurately simulating fault transients. The method includes the identification of fault section for a transmission line with a UPFC using a wavelet-fuzzy discriminator. Features are extracted using a wavelet transform and the normalised features are fed to the fuzzy logic systems for the identification of fault section. After the identification of the fault section, the control shifts to the differential equation-based fault locator that estimates the fault location in terms of the line inductance up to the fault point from the relaying end. Shunt faults are simulated with wide variations in operating conditions and a pre-fault parameter setting. The instantaneous fault current and voltage samples at the sending and receiving ends are fed to the designed algorithm sample by sample, which results in the fault location in terms of the line inductance. The proposed method is tested for different fault situations with wide variations in operating conditions in the presence of a UPFC.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.