Abstract

Among special insulation tests for DC power converter transformers, polarity reversal tests can be substituted by applied AC voltage tests from a stress similarity in oil ducts. In order to investigate equivalent levels of other insulation tests to polarity reversal tests, the dielectric strength of a transformer at polarity reversals was examined by use of a model of typical oil/paper composite insulation. From the comparison of polarity reversal and other insulation tests, it was found that dielectric strength of transformer insulation at polarity reversals is phenomenally similar to that under switching impulse stresses. Equivalent AC test voltage to polarity reversal test was also estimated from the experimental results. The breakdown characteristics of polarity reversal tests showed that partial discharges at polarity reversals impose less harmful stress on insulation barriers than those at usual AC or impulse tests.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.