Abstract
According to the latest research, nanofluids as a possible future substitution for high-voltage equipment insulation have the potential to enhance the heat transfer and insulation properties of their base fluids. Dielectric properties are represented by breakdown strength (AC, DC, lightning) and dielectric performance as a set of quantities including dissipation factor, permittivity, and volume resistivity. In this study, natural and synthetic esters were mixed with C60 nanoparticles. Samples were examined for dissipation factor, relative permittivity, and volume resistivity at temperatures between 25 °C and 140 °C to monitor changes in dielectric performance with rising temperature, in accordance with IEC 60247. In addition, the samples were tested for AC breakdown voltage (using mushroom-like electrodes with a gap distance of 1 mm) and evaluated using the Weibull distribution statistical method. These measurements allowed complex evaluation of the examined mixtures and the determination of optimal concentration for each ester-based nanofluid.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.