Abstract
The aim of the work was to prepare and test a paper-oil insulation system according to the recommendations of CIGRE (Conseil International des Grands Réseaux Électriques) with the parameters X = 50% and Y = 30%. Pressboard was moistened to a water content of (5.0 ± 0.2) wt.% The loss tangent was measured using a DIRANA meter (FDS-PDC dielectric response analyzer) in the frequency range 10−4 Hz–5000 Hz for 6 temperatures from 293.15 K to 333.15 K with a step of 8 K. The waveforms simulated by the DIRANA software were fitted to the experimental dependence of the loss tangent. The fitting process was performed using two methods. In the first method, the measuring temperature value as well as X and Y values were entered into the software. The estimated moisture content of the insulation varied from about 1.4 to about 5.2 wt.%. The average value of moisture content was (3.73 ± 1.11) wt.%. In the second method, only the measuring temperature value was entered into the software. This improved the quality of matching. The estimated average moisture content was (5.83 ± 0.25) wt.%. It was found that the dimensions of the oil channel clearly affected the quality of the fitting process. By not taking into consideration real values of oil channel, the quality of the moisture content estimation was significantly improved.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: Energies
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.