Abstract
There are many irreplaceable advantages of high temperature superconducting (HTS) fault current limiter, applying in electric utilities. It is expected to be able to solve excessive fault current problems and to enhance safety and stability of power systems. In this paper, the R and D of an improved bridge-type 10.5 kV three-phase superconducting fault current limiter (SFCL) was present. Each phase adopted a HTS coil with inductance of 6.2 mH. The three coils wound with 8,571 m Bi2223/Ag tapes totally. After installation at a 110 kV/10.5 kV substation in Hunan Province of China, the performances of the whole SFCL were tested, including a three-phase-to-ground short circuit experiment at the pre-setup short circuit point. And then, the SFCL was put into operations in the 10.5 kV power grids for more than 11000 h. About 3 years later, the SFCL was moved, reinstalled, and put into operation again since February 16 of 2011 at a 10.5-kV superconducting power substation located in Baiyin, Gansu Province of China. In this paper, the redesigned and manufactured cryostats with nonmagnetic stainless steel, tests, and long-term operations of the SFCL in 10.5 kV power grids were also described in detail.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.