Abstract
Propagation of short high-voltage pulses along a 6-m-long twin line was studied in the presence of corona discharge. The experimental setup included a twin-line arrangement, a 100-kV, 5-ns pulse generator, voltage and current probes, and photomultipliers. The dependencies on line geometry and wire conductivity and on pulse voltage and polarity have been studied. PSpice and electrostatic simulations are presented; the latter are compared to still photos of corona discharge. Of most interest was the finding that the discharge was very much asymmetric when one of the pulser's terminals was grounded, even when the line height was much greater than the distance between the wires. This effect will be pronounced to heights of hundreds of meters. Pulsed corona study on NiCr resistive wires revealed intense pulse decay: only 1% of the launched energy reaches the end.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.