Abstract
Partial discharge (PD) characteristics in air, argon and helium at pressures between 101 kPa (760 Torr) to about 0.27 kPa (2 Torr) under 60 Hz AC energization were studied with various electrode arrangements. Measurements are presented for two representative electrode configurations, (1) needle-plane, with 20 mm spacing and a dielectric barrier, and (2) a twisted pair of insulated conductors. Typical PD current pulse waveforms are presented. Difficulties in adhering to measurement guidelines defined by the IEC 60270 standard are described, and suggested modifications of the standard procedures are presented for measurement and calibration for low-pressure PD.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.