Abstract

Metal oxide arresters (MOA) are widely used for over-voltage protection of power facilities in 10 kV distribution networks, and it is hard to determine the failure ones. This study presented an online monitor for 10 kV MOA used in substation. Firstly, with simulation on electromagnetic transient program (EMTP), the authors found that the resistive component of leakage current flowing through the MOA could reflect its health status. Then the principle of detecting the resistive leakage current flowing MOA by the harmonic analysis method is introduced. Finally, a remote monitoring system for MOA based on wireless communication technology is built and testing experiments of monitoring the health status of MOA has been done.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.