Abstract
This paper presents partial discharge (PD) measurement techniques using a commercial sensor, High-Frequency Current Transformer (HFCT). An Output signal from HFCT is read by a digital oscilloscope and compared with the reading of convensional that PD detector. When PD occurs, the signals detected using high impedance that has a long time of oscillations and cause the delay of next reading of PD signals. To avoid this issue, the time of oscillations must be reduced by installing a damper which is a resistor connected in parallel between the sensor and the oscilloscope. The result of the measurement shows that the damper has the same reading on peak values as read by the convensional PD detector.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: IOP Conference Series: Materials Science and Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.