Abstract
Achieving energy efficiency by improving the operating method of the system used in existing buildings is attracting considerable attention. The Building Design Criteria for Energy Saving was established to induce energy saving design in the domestic construction field, and the introduction of a free-cooling system, such as an economizer system, as an item of the mechanical sector, was evaluated. The economizer is an energy saving method that reduces the building load by introducing outdoor air through damper control according to the indoor and outdoor conditions. The system consists of dry-bulb temperature control and enthalpy control and the mixed air temperature is kept constant in the conventional economizer controls. On the other hand, in dry-bulb temperature control, when the set value of the mixed air temperature is changed according to the load, additional energy savings are expected compared to the conventional control method. Therefore, this paper proposes an economizer control that makes the mixed air temperature variable according to the load in a Constant Air Volume single duct system. For this, a load prediction is needed and an Artificial Neural Network is used for the load prediction. In addition, the relationship between the mixed air temperature and energy were analyzed using the BIN method and TRNSYS 17. Based on the results of previous analysis, a control method which predicting the load using Artificial Neural Network and controlling the mixed air temperature according to the predicted load in the dry-bulb temperature control of a Constant Air Volume single duct system is proposed and the proposed control was applied to the dynamic simulation program and compared with the conventional control. The results show that the temperature of each room was 21–23 °C in summer and 22.5–26 °C in winter when the economizer was controlled using the proposed control method and the energy consumption analysis showed that 19% of the energy was reduced compared to the conventional method when the proposed method was controlled.
Highlights
Reducing greenhouse gas emissions and energy use is a global issue [1,2]
The control method proposed in this study aims to control the mixed air temperature variable according to the load, unlike conventional intake ratio were determined according to the state of the outdoor air and return air, and, the damper was opened
The control method proposed in this study aims to control the mixed air temperature variable according to the load, unlike conventional dry-bulb temperature control
Summary
Reducing greenhouse gas emissions and energy use is a global issue [1,2]. Energy efficiency by improving the operation method of the system used in existing buildings is attracting considerable attention. As one of the active items in the building design criteria, it evaluates free-cooling systems, such as the economizer, which is one of the energy efficiency methods by improving the operating method. This evaluation criterion shall be rated when the outdoor cooling system such as the economizer system is applied to reduce the cooling load by introducing outdoor air during intermediate season [4]
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.