Abstract

AbstractWhen ground‐fault problems occur on a cable line, immediate fault location and restoration are required. Therefore, various new methods to locate the fault point instantaneously have been investigated to replace such conventional methods as the Murray loop method and the pulse radar method [1]. These methods require a long time to locate the fault point. One possible fault location method is to sense the temperature rise following a ground fault using a fiber optic distributed temperature sensor. Application of this method was found feasible through sensing the temperature rise at a ground‐fault test using a thermocouple as a temperature sensor with test cables [4].A power/optical composite cable was prepared experimentally and after verifying its thermal mechanical performance, the temperature rise at an incidence of a fault was determined and the anticipated performance was demonstrated in a ground‐fault test. This article describes the outline of the test.