Abstract

This paper describes the results of tests and discussions carried out to develop a system for partial discharge monitoring in GIS. They include the propagation characteristics of partial discharge pulses in each GIS component, as well as the test results obtained using an actual 300-kV GIS. We also report the results of verification test on the GIS partial discharge monitoring and location system developed by the authors. © 1999 Scripta Technica, Electr Eng Jpn, 129(2): 40–50, 1999

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.