Abstract

This paper describes the development of a new islanding detection system based on the change ratio of harmonic admittances, voltages and currents of the power system between the response measured when the main utility supply is connected to the distributed generation site and that measured when the distributed generation site is operating in islanding. The results of verification tests conducted at the Akagi Test Center of CRIEPI and at several hydroelectric power plants of Kansai Electric Power are also described. No disturbance to the grid is caused through this mechanism because it uses only harmonics characteristics without injecting any active influence to the grid. In addition, the islanding condition can be detected accurately regardless of the grid state even when the local generation power and the loads in the islanding system are perfectly balanced.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.