Abstract

This paper describes the main characteristics and the performance of a saturated core type fault current limiter (FCL) rated 45 MVA (33 kV-800 A) to be provided by ASG Power Systems. The FCL, which has been submitted to preliminary laboratory testing, will be installed at a 275/33 kV substation in the U.K. and will reduce the fault current by 38%. The device is based on an open geometry of the magnetic cores which allows reduced size and the weight. Magnetic saturation of the cores is obtained by means of two magnesium diboride (MgB2) magnets. A numerical model of the FCL has been developed and validated and the interaction of the device with the power grid has been investigated. Details and results of the model are also discussed in the paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.