Abstract
It is well known that line switching operations like reclosing are able to cause transient power oscillations which can stress or damage turbine generators. This paper presents a reclosing scheme to reduce the shaft torsional torques of turbine generators by inserting an additional reactor. In this paper, the turbine generator shaft is represented by a multi-mass model to measure torsional torques generated in the shaft between the turbine and the generator. Transmission systems based on actual data from Korea are modeled to verify the proposed scheme using ElectroMagnetic Transient Program (EMTP) software. The simulation results clearly show the effectiveness of the proposed scheme and torsional torque can be reduced by applying the proposed scheme.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.