Abstract

A novel mitigation system against hydrogen-air deflagrations in nuclear power plant buildings is proposed and developed through a series of field experiments using explosion vessels of different volume sizes. The mitigation system is installed on the outer surface of the vessels, and it comprises flame arrester and explosion air bag. The flame arrester is made by stacking 10–20 sheets of fine-mesh wire screens, and the air bag is connected for holding explosion gas. The successful mitigation mechanism is the sequence of pressure-rise reduction by the air bag expansion, flame quenching by the flame arrester, and the slow burning of the gas mixture sucked from the air bag back into the vessel due to the negative pressure caused by the rapid condensation of water vapor inside the vessel. Necessary conditions for the successful mitigation system are discussed, and the practical unit size of flame arrester sheet is recommended.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.