Abstract

A 40l/h Helium Liquefier has been commissioned by the Technical Institute of Physics and Chemistry, Chinese Academy of Sciences. A measurement and control system based on Siemens PLC S7-300 for this Helium Liquefier is developed. Proper sensors are selected, for example, three types of transmitters are adopted respectively according to detailed temperature measurement requirements. Siemens S7-300 PLC CPU315-2PN/DP operates as a master station and three sets of ET200M DP remote expand I/O operate asslave stations. Profibus-DP field communication is used between the master station and the slave stations. The upper computer HMI(Human Machine Interface) is compiled using Siemens configuration software WinCC V7.0. The upper computer communicates with PLC by means of industrial Ethernet. A specific control logic for this Helium Liquefier is developed. The control of the suction and discharge pressures of the compressor and the control of the turbo-expanders loop are being discussed in this paper. Following the commissioning phase, the outlet temperature of the second stage turbine has reached 8.6K and the temperature before the throttle valve has reached 13.1K.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call