Abstract

The nozzle chamber, in which water is sprayed into the air stream using mechanical nozzles, is the main unit for these processes in central air conditioning systems (AHUs). The types of nozzles used do not have a sufficiently high effect of interfacial surface forming due to increased metal usage and the broad total dimensions of certain chambers, i.e., they do not have intensive heat and mass transfer. The authors performed testing of the apparatus in the direct iso-enthalpic air cooling mode to improve the performance of the nozzle chamber. Thus, the experiments conducted confirm the relatively high efficiency of FET operation at small values of irrigation coefficient B ≥ 1.0. The area highlighted is characterised by the unstable operation of other nozzle types. Therefore, FET nozzles can be operated at irrigation factor values B = 0.1…1.0. Experiments have shown that this equation is applicable for practical calculations, with a relative error of ±6.7%. The aerodynamic resistance of the spray chamber nozzle chambers is also according to the data not exceeding 160 Pa.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.