Abstract

AbstractThis paper presents a novel detection device for deteriorated zinc‐oxide (ZnO) surge arresters. It is necessary to understand the state of ZnO surge arresters for AC traction substations under operation. The waveform distortion of leakage currents can be detected through an increase in multiple harmonic currents; therefore, this effect was employed to develop a device for diagnosing damage to the surge arrester. By adopting a Rogowski coil and band‐pass filters, we can obtain more output of the 5th–15th order harmonic currents in comparison with conventional devices. If the threshold value of harmonic elements is exceeded, the lights on the device may light up to indicate the deterioration. The validity of the device was verified by artificial deterioration tests using damaged ZnO elements and a capacitor. This developed device could indicate the soundness of the surge arresters that are in proper working order while being under the influence of feeding voltages, which include harmonic voltages.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.