Abstract

Capillary tube, suction line heat exchangers (CT-SLHX) are widely used as expansion devices in small-capacity refrigeration and air-conditioning systems to enhance the refrigeration capacity and ensure that superheated refrigerant vapor enters the compressor. To calculate the mass flow rate through a capillary tube, a reliable non-adiabatic capillary tube model is necessary. Most previous correlations were developed separately for subcooled liquid inlet conditions and for saturated two-phase inlet conditions; so the models are not continuous at the saturated liquid point. An empirical model that is continuous at the saturated liquid point was developed and is introduced herein with a new dimensionless π parameter. This new empirical model is validated using experimental measurements available in the literature for the refrigerants R-134a, R-600a, R-410A, R-152a, and R-22. The new correlation shows good agreement with the experimental data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.