Abstract

This paper discusses the results of a basic study for the development of 500 kV XLPE power cables. The authors have established that the factors that decide the performance of today's XLPE cables are impurities in the insulator and protrusions on the semiconductive layer, and that the insulation performance of XLPE power cables is determined by the size of these defects. In model tests of XLPE power cables, the minimum insulation breakdown stress of cables was determined, to set the design values for 500 kV XLPE cable. As a result, it was found that it is possible to design cables having an insulation thickness of 25 mm.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.