Abstract

AbstractA three‐in‐one HTS cable has been developed. Its cable core is composed of a conductor and a shield wound with BSCCO and electrical insulation of the PPLP. The three cable cores are covered in thermal insulated stainless corrugated pipes. The BSCCO wires represent a dramatic innovation by virtue of a newly developed process named Controlled Over‐Pressure (CT‐OP). As a new cable technology, a 350‐m thermal insulation pipe was tested for 7 months to find that the life of the vacuum intensity is more than 10 years. The HTS cable with tension members was designed for installation into an underground duct. In addition, a fault current of 23 kA, 0.63 s, was applied to a sample cable with no damage to the BSCCO wires or the cable insulation. These technologies will be applied to the Albany project in the USA. © 2007 Wiley Periodicals, Inc. Electr Eng Jpn, 162(1): 15–24, 2008; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20577

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call