Abstract

This paper presents the development and validation of a two-zone model to predict fire development in a compartment. The model includes the effects of the ceiling jet on the convective heat transfer to enclosure walls and, unlike existing models, a new concept of surrogate fuel molecule (SFM) to model multi-fuel combustion, and a momentum equation to accurately track the displacement of the smoke layer interface over time. The paper presents a series of full-scale fire experiments conducted in the IUSTI fire laboratory, involving different combinations of solid and liquid fuels, and varying the compartment confinement level. The model results are compared to the experimental data. It was found that for all fire scenarios, the experimental trends are well reproduced by the model. The SFM concept predicts oxygen and carbon dioxide concentrations in the extracted smoke to within a few percent of the measurements, which is a good agreement considering the sensitivity of the model to chemical formulas and combustion properties of fuels. Comparison with other measurements, namely average gas and wall temperatures, is also good. For the large fires reported in this study, the impact of the ceiling jet leads to a slight underestimation of wall temperatures, while the model gives conservative estimates for small fires.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call