Abstract

High-temperature superconducting (HTS) transformers are verypromising candidates for application in electrical power engineering. Theirmain advantages are reduced size, weight, better efficiency and reducedpotential fire and environmental hazards. We have designed, constructed andtested a 100 kVA HTS power transformer operated at 77 K. The nominal primaryand secondary currents (voltages) are 18 A (5.6 kV) and 92 A (1.1 kV),respectively. No-load tests, short-circuit tests and load tests provedrepeatedly that the transformer has the rated capacity. HTS winding losses of20.6 W and iron losses of 403 W were measured.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.