Abstract
A perfluorocarbon (PFC) immersed 275 kV power transformer with compressed SF/sub 6/ gas insulation has been under development. This paper clarifies the AC partial discharge inception voltage and time characteristics of PFC immersed insulation and also clarifies that a prototype 275 kV 100 MVA three-phase transformer could be operated without any trouble during long-term overvoltage tests. This prototype proved that it had AC partial discharge inception strength of higher than 1.5 times the AC test voltage and lightning impulse breakdown strength of 1.5 times the test voltage. A 275 kV, 250 MVA three-phase power transformer was developed and operated at the outdoor substation of the Chubu Electric Power Co., Japan. This transformer has been successfully operated to date and a detailed internal inspection of the transformer was carried out after one year and 9 months of successful practical operation. No significant abnormal condition was recognized. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.