Arcing fault is an overvoltage that usually occurs in the power system network, and it is necessary to monitor this phenomenon in electrical equipment. This paper presents the Rogowski coil (RC) as an arcing fault sensor. Finite element method (FEM) software used for analysing the RC magnetic flux density with two types of RC with the different turns and size demonstrated. The sizing of RC based on the 240 mm2 cross-link polyethene (XLPE) 11 kV underground cable. The prototypes of the RC sensors were designed using Solidworks software and three-dimensional (3D) printer for fabrication purposes. The main objective of the experiment is to investigate the RC effect with high magnetic flux density by implementing in real measurement. An experimental setup for real arcing fault with various voltages (up to 15 kV) was conducted to verify the RC performance, such as sensitivity and bandwidth range. The result has shown that the bandwidth of RC 1 is higher than RC 2 in all measurement by 22.6%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Materials Science and Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.