Abstract

ABSTRACTRenovation of water and central heating pipelines is a very costly and time‐consuming process; therefore, a way to prioritize the limited resources between different parts of the systems is very important. The risk for corrosion damage can be assessed from the resistivity of the ground, because the processes facilitating the metal oxidation also affect the resistivity. However, galvanic resistivity mapping is time consuming and work‐intensive in paved areas. To determine the resistivity in the vicinity of pipes two different resistivity methods were applied: electrical resistivity tomography using galvanic coupling, and the logistically easier and rapid electrostatic measurements using capacitive coupling. The two methods were tested in a series of experiments undertaken in the province of Scania in southern Sweden with the aim to acquire a better knowledge about the electrical resistivity of the soil surrounding the heating and water distribution pipes, in order to better assess the corrosivity of the environment. From the experiments it is shown that the electrical resistivity tomography and electrostatic methods mostly give comparable results for the shallow investigated depths in focus here, where differences might be caused by different sensitivities and noise characteristics. In the case of both methods, it is shown, with the help of modelling of the different expected ground models including the pipes, that the pipes only influence the data in cases of pipes of very large diameters or those buried at a very shallow depth, even without any protective surface coating. The missing influence of the pipes on the data makes the methods very applicable for knowing the resistivity of the soil surrounding the pipes and thus evaluation of corrosion risk.

Highlights

  • Extensive networks of buried pipes for water transport and heating exist all over the world

  • A series of experiments were undertaken in the province Scania in southern Sweden with the aim to acquire a better knowledge about the electrical resistivity of the soil surrounding heating and water distribution pipes, in order to better assess the corrosivity of the environment

  • When looking at all the combined results, the models interpreted from the electrical resistivity tomography (ERT) data and the electrostatic data are similar along much of the lines, but there are significant differences that need to be explained

Read more

Summary

Introduction

Extensive networks of buried pipes for water transport and heating exist all over the world. The replacement of pipes is a very costly process, and a Corrosion of a pipe is difficult to detect precisely without uncovering long stretches of pipe and visually inspecting Engineers Several factors influence the corrosivity of the environment around the pipes such as pH, ion content and moisture content of the soil, which are tied to lowering the resistivity of the soil. A series of experiments were undertaken in the province Scania in southern Sweden with the aim to acquire a better knowledge about the electrical resistivity of the soil surrounding heating and water distribution pipes, in order to better assess the corrosivity of the environment.

Results
Discussion
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.