Abstract
The objective of this work is to investigate experimentally the effects of mixture concentrations, source temperature, flow rate of condenser cooling water and air flow rate in the cooling tower on the Coefficient of performance (COP) and η ex (exergetic efficiency) values of vapour compression heat pump systems. The experimental apparatuses consist of a vapour compression heat pump conducting according to the liquid to air principle, refrigerant mixture unit, cooling tower, measuring elements and other auxiliary equipment. Refrigerants R11, R12, R22 and six of their binary mixtures which contain about 25%, 50% and 75% mass fractions of R22 were tested. The experiments were performed in the region of source temperatures from 18 to 28°C and flow rates of condenser cooling water from 500 to 1250 kg/h. Four different air flow rates were chosen in those experiments in the cooling tower. To determine the efficiency of the chosen parameters on the system and optimum working conditions, an experimental design method suggested by Genichi Taguchi was used. In this study, it was observed that the COP and η ex increased with the addition of R22 to the system over R11 and R12 pure refrigerants.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.