Abstract
This paper presents a study for determining the maximum amount of PV solar generation that can be connected in a 27.6 kV feeder of a distribution utility - London Hydro. Various factors such as steady state voltage rise, Temporary Over Voltage (TOV), short circuit current and harmonic contributions, that could potentially constrain DG connectivity are investigated. Load flow studies with PSS/E and electromagnetic transient simulation studies with EMTDC/PSCAD software are utilized for performing the above investigations. It is shown that harmonic amplification due to network resonance could potentially be the limiting factor for PV solar connectivity in this distribution feeder. This paper also makes a case that the conventional Connection Impact Assessment (CIA) studies for DG connections need to be made broader to include such harmonic aspects.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.