Abstract

The condensation occurs between the building envelope layers is important for both human health and the functioning of the layers. Freezing of the condensed water in cold weather region like 3rd degree-day region means another solid layer that creates freeze-thaw effect. In this study, the amount of condensation between layers for the 3 most commonly used wall types is investigated in Kütahya. The condensation phenomena is determined by Glaser Diagram Method and the condensation amount is calculated by considering climatic data. Wall 3 gives the best result and that one has 0,001696833 kg/h.m2 at 0 ºC, it is 0,002142743 kg/h.m2 at -21 ºC condensed water amount due to low outside temperature.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.