Abstract
This paper deals with the determination of analytical calculation error of magnetic field of high-voltage cable lines in two-point bonded cable shields caused by non-uniformity of the current distribution in the shields. The relative error is determined by comparing numerical calculation of magnetic field obtained in the COMSOL Multiphysics software with the analytical one. It is shown that the maximum value of relative error does not exceed 8 %. The obtained error values are verified by testing the numerical calculation and confirmed by results of experiment. In paper proves the correctness of the analytical calculation of magnetic field of cable lines at the points of its normalization, which is carried out without taking into account the non-uniform current distribution in the cable shields.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.