Abstract
There are two sets of standards available in the Chinese market that specify the design requirements and operating tests for arc fault detection devices (GB/T 31143) and arcing fault detectors (GB 14287.4) respectively. While arcing fault detectors (AFDs) are claimed to have passed GB 14287.4 standard tests, it remains unclear whether these AFDs can pass GB/T 31143 standards and effectively detect arc fault signals. This study experiments to explore the operational performance of AFDs in the Chinese market based on GB/T 31143 standards, revealing that not all AFDs can pass this test and provide adequate protection for people’s lives and property. The main reason for the failure is that the arcing characteristics, such as flat shoulders and reduced amplitude, of the signal are easily masked by other branch circuit loads.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.